Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)10 Provide means to access car top from first floor lobby.
MO Minimum : Elevators (A) - Hoistways (A)17 There was a drain line running in the Northwest corner the length of the elevator hoistway 5/15/2020
MO Minimum : Elevators (A) - Hoistways (A)3 Adjust top floor interlock as the hoistway door was stopping on the contact bar on the housing of the interlock 5/15/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x 2. All automatic passenger elevators shall be provided with an alarm bell capable of being activated from inside the car and audible outside the hoistway. This inspection item was never performed. 9/13/2018
MO Minimum : Elevators (D) - Brakes (D)2 x x 5. For passenger elevators and all freight elevators, the brake shall be tested for compliance with applicable requirements. Place the load (125%) in the car and run it to the lowest landing by normal operating means. The driving machine shall safely lower, stop, and hold the car with this load. Never checked for 5-year testing. This is a re-inspect. 8.11.2.3.4 9/13/2018
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be code compliant.
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self locking / self closing
MO Minimum : Elevators (H) - Machine Rooms (H)2 MACHINE ROOM DOOR SHALL BE SELF CLOSING / SELF LOCKING
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door required to be self closing self locking
MO Minimum : Elevators (H) - Machine Rooms (H)3 Seal all machine room wall penetrations.
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Machine room lighting in front of car #2 controller, plug in light not acceptable.
MO Minimum : Elevators (H) - Machine Rooms (H)8 Provide feeder location on main line and 110v disconnect.
MO Minimum : Elevators (H) - Machine Rooms (H)8 GFCI shall be wired per code and operational.
MO Minimum : Elevators (I) - Pits (I)1 Means shall be provided to allow water to reach sump pit
MO Minimum : Elevators (I) - Pits (I)1 7. All pits shall be kept dry, clean and free of equipment or material not relating to the operation of the elevator. Miscellaneous debris in pit. Needs to be cleaned out. 5/15/2020
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) 8. A permanent lighting fixture shall be provided in all pits to provide an illumination of not less than five (5) foot-candles at the pit floor. The fixture switch shall be provided and accessible from the pit access door. No lighting in this pit. 5/15/2020
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x x 1. On any type of elevator, the suspension compensation and governor ropes shall be replaced when their actual diameter is reduced below the value shown in Table 8.11.2.1.3(cc)(3). These ropes are undersized below value in table and shall be replaced. Measurement taken at 10th floor. This is a re-inspect and has been red tagged. 8.11.2.1.3(cc)(3) 9/13/2018
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x 4. The governor rope pull-through and pull-out forces shall be tested to determine conformance with the applicable requirements, and the adjustment means shall be sealed. Never checked for 5-year testing. This is a re-inspect. 8.11.2.3.2(b) 9/13/2018
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x 6. Type B safeties shall stop the car with the rated load within the required range of stopping distances for which the governor is tripped. Never checked for 5-year testing. This is a re-inspect. 8.11.2.3.1(a) 9/13/2018
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)7 x x 3. The tripping speed of the governor and the speed at which the governor overspeed switch, where provided, operates shall be tested to determine conformance with the applicable requirements and the adjustable means shall be sealed. Never checked for 5-year testing. This is a re-inspect. 8.11.2.3.2(a) 9/13/2018
MO Minimum : Elevators (S) - Fire Service (S)1 x 9. Firefighters’ emergency operation shall be tested to determine conformance with the applicable requirements. This inspection item was never performed. This is a re-inspect. 8.11.2.2.6 9/13/2018
MO Minimum : Elevators (S) - Fire Service (S)1 x The fireman's emergency service operation phase I key switch in the lobby did not match the phase II key switch in the car. 5/15/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate in machine room.