Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be on display in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) x Counterweight runby is below minimum. Hoist ropes need to be shrotened. Re-inspection required.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Place current state operating certificate in elelvator machine room. Rule 40-5.100(2)
MO Minimum : Elevators (S) - Fire Service (S)1 x The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: The car door “close” button did not operate on phase II operation. 6/22/2020