Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not operate without normal power 8/10/2022
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed 8/12/2022
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5.2 Collection of Oil Leakage x Remove scavenger pump from pit. Cylinder drain lines need to drain into pit collection container of no more than 5 gallon capacity. 5/3/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No MCP 8/12/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) No maintenance records on site 8/12/2022