Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Right handrail should be replaced due to cracks
A17.1-1996 : Escalators 7.3 - Handrails 802.2 Need to replace left handrail.
A17.1-1996 : Escalators 8.12 - Steps, step chains, and trusses 802.7 Replace all worn step rollers. 8.6.8.7
A17.1-2016 : Elevators 7.19 - Maintenance records 8.6.1.2.1(c) Provide job specific wiring diagrams.
A17.1-2016 : Elevators 7.19 - Maintenance records 8.6.1.2.1(a) Provide maintenance control programs documents.
A17.1-1996 : Escalators 7.3 - Handrails 802.4 Right handrail needs to be replaced due to cracks.
A17.1-2016 : Elevators 7.3 - Handrails 8.6.8.1 Right handrail Shall be replaced
A17.1-2016 : Elevators 7.7 - Combplate and comb step impact device 8.6.8.15.18 Walk on plate switches shall be made operable
A17.1-2016 : Elevators 8.4 - Drive machine and brake 8.6.8.15.4 Escalator brake torque test not performed. Re-inspection required
A17.1-1996 : Escalators 7.3 - Handrails 1008.2m Handrails The right side hand rail has degraded and shall be replaced.
A17.1-2016 : Elevators 8.4 - Drive machine and brake 8.6.8.15.4 x The brake torque could not be tested on the initially due to the need for a specific tool. Reinspection for the brake torque is required.