A17.1-2016 : Elevators
|
7.19 - Maintenance records
|
8.6.1.2.1(a)
|
|
|
Provide all maintenance control program documents.
|
|
A17.1-2016 : Elevators
|
7.19 - Maintenance records
|
8.6.1.2.1(c)
|
|
|
Provide job specific wiring diagrams.
|
|
A17.1-1996 : Escalators
|
8.12 - Steps, step chains, and trusses
|
802.7
|
|
|
Replace all worn step rollers. 8.6.8.7
|
|
A17.1-1996 : Escalators
|
8.12 - Steps, step chains, and trusses
|
802.7
|
|
|
Replace all worn step rollers.
|
|
A17.1-1996 : Escalators
|
7.3 - Handrails
|
802.4
|
|
|
Not working correctly.
|
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
8.6.8.13 Escalator Cleaning
|
|
|
Unit clean down needed.
|
|
A17.1-1996 : Escalators
|
7.3 - Handrails
|
1008.2m Handrails
|
|
|
Handrail on the left side has degraded and shall be replaced.
|
|
conversion
|
conversion
|
n/a
|
|
|
Repair step demarcation lights.
|
11/21/2018
|
A17.1-1996 : Escalators
|
8.4 - Drive machine and brake
|
1008.2d
|
x
|
x
|
Brake failed torque test and fails to burnish, unresponsive. Possible oil contamination. Replace drive machine brake. Red tagged unit.
|
11/20/2020
|
A17.1-1996 : Escalators
|
8.4 - Drive machine and brake
|
804
|
x
|
x
|
Failed brake test
|
4/17/2023
|