MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.11 Runby (Re-Inspection)
|
x
|
|
Need to shorten ropes. Re-inspection required
|
4/14/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Elevator machine room air conditioner is not working. 90 degrees F at time of inspection. Repair
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required.
|
|
A17.1-2016 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
8.6.4.19.16
|
x
|
|
Door restrictor inoperable (damaged), repair car door restrictor
|
4/3/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.11.2.1.1(e) Car Lighting
|
|
|
Emergency lights do not work.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone does not work on battery back-up power.
|
2/25/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair emergency phone - does not work with power off.
|
4/18/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Full load test incomplete. Test car buffer with rated load at rated speed. Test car safeties with rated load at rated speed. Test driving machine brake with 125% of rated load.
|
4/3/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
8.6.2.5
|
|
|
Suspension ropes are rouged and undersized and need to be replaced. REINSPECT WITHIN 30 DAYS
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing
|
8.6.4.11
|
x
|
|
Clean elevator car top.
|
2/25/2021
|
conversion
|
conversion
|
n/a
|
|
|
Install tack wiring in conduit or duct in machine room
|
|
conversion
|
conversion
|
n/a
|
|
|
Pit should be clean and drive remove water and debris
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
18 repair door restrictor
|
4/29/2019
|