Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Full load test incomplete. Test car buffer with rated load at rated speed. Test car safeties with rated load at rated speed. Test driving machine brake with 125% of rated load. 4/3/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone does not work on battery back-up power. 2/25/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.11.2.1.1(e) Car Lighting Emergency lights do not work.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Repair emergency phone - does not work with power off. 4/18/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Elevator machine room air conditioner is not working. 90 degrees F at time of inspection. Repair
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.6.2.5 Suspension ropes are rouged and undersized and need to be replaced. REINSPECT WITHIN 30 DAYS
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing 8.6.4.11 x Clean elevator car top. 2/25/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) x Need to shorten ropes. Re-inspection required 4/14/2023
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.19.16 x Door restrictor inoperable (damaged), repair car door restrictor 4/3/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required.
conversion conversion conversion - reinspect x 18 repair door restrictor 4/29/2019
conversion conversion n/a Install tack wiring in conduit or duct in machine room
conversion conversion n/a Pit should be clean and drive remove water and debris