Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)2 Install a closer on the new machine room door 9/25/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Repair the emergency phone as the incoming line is dead it has no dial tone. 9/25/2025
A17.1-2016 : Elevators 11.1 - Access to Machine Room/Machinery Space/Control Room/Control Space 2.7.3 Install a door closer on the machine room door as it is to be self closing self latching always locked outside never locked inside , use a mechanical room door lock. 3/13/2026
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Have the fire extinguisher re certified 3/13/2026
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x Check out the operating of the sump pump as it re cycles every 40 seconds. The check valve does not keep the water from returning to the pit.
conversion conversion n/a Obtain and display a current state operating certificate in the machine room. 8/1/2018
conversion conversion n/a I recomend replacing the lower level door jamb as it is rustsed real bad along the bottom for about 1 foot up from the floor. This is going to cause the door not to close properly inthe near future. 8/1/2018
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Obtain and display a current state operating certificate in the machine room 8/31/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Obtain and display a current state operating certificate in the machine room 3/13/2026