Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 5/5/2021
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. 5/5/2021
MO Minimum : Elevators (H) - Machine Rooms (H)4 Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in elevator machine rooms. 11/3/2023
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. 5/5/2021
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an overspeed valve. With this elevator having an installation year of 2003, a category 5 test shall be performed on the overspeed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. (This item is for notification purposes). 10/27/2023