A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Have the emergency phone repaired as the incoming line is dead it has no voltage on it.
|
3/19/2026
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Have the emergency phone repaired as it has no dial tone the incoming line is dead
|
|
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5a Lighting
|
|
|
Repair the machine room light as 20 foot candle of light is required at the floor level
|
|
|
A17.1-1996 : Elevators
|
2.4 - Machine space
|
101.1a
|
|
|
Repair the hole cut into the machine room ceiling back to the 1 hour rated assembly.
|
8/3/2021
|
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1206.1h
|
|
|
Have the expired fire extinguisher re-certified.
|
3/19/2026
|
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1206.1h
|
|
|
Have the fire extinguisher re certified it expired.
|
|