Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.4 - Machine space 101.1a Repair the hole cut into the machine room ceiling back to the 1 hour rated assembly. 8/3/2021
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h Have the expired fire extinguisher re-certified.
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Have the emergency phone repaired as the incoming line is dead it has no voltage on it.