Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) Fire extinguisher needs to be serviced. 8/10/2020
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5c Receptacles A duplex GFCI receptacle rated at not less than 15 A, 120 V shall be provided in each machine room and machinery space. 11/7/2023
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2b (Clean Machine Room) The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. 11/7/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The signage for “In Case of Fire” is missing on a number of landings. Install signage that conforms to the building code this elevator was installed to meet. 11/7/2023
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.
MO Minimum : Elevators (H) - Machine Rooms (H)4 Remove all the non elevator related items from the elevator machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Provide current year tested fire extinguisher in the elevator machine room.
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(5) Oil Leakage Collection Remove oil return lines going back to the tank. Provide each piston means to collect oil in the pit.
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 4/30/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Reinspection required. 6/17/2022
conversion conversion conversion - reinspect x Repair inoperable emergency phone 5/28/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 4/29/2020