Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current copy of the state operating certificate is to be displayed in the machine room
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 fire service test log must be filled out monthly, currently it is only filled out quarterly 3/4/2020
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.11.3.1.2(j) machine room fire extinguisher inspection tag is from 2019, have it inspected and tagged annually
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log monthly fire service test log is not being filled out
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.11.3.1.5(a) pit is wet, maintain dry pit
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate post a new copy of the state certificate in the machine room every year
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting replace burnt out cab ceiling light bulbs
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits standing water in the pit, maintain dry pit 3/4/2020
A17.1-2016 : Elevators 5.15 - Overspeed Valve 3.19.4.7.5(a) The next weight test on the overspeed valve is due in 2023 1/19/2022