Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x In car emergency telephone shall work. 3/2/2020
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 2/18/2022
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 3/7/2023
A17.1-1996 : Elevators 3.16 - Traveling cables and junction boxes 102.1 The traveling cables shall be hung properly. 3/7/2023
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. 3/7/2023
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an overspeed valve that in not sealed. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. 3/10/2023
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 3/10/2023
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 3/10/2023
A17.1-1996 : Elevators 3.16 - Traveling cables and junction boxes 1001.2(c)(22) The wiring bound to the traveling cables is not listed or approved for use as an elevator traveling cable. It shall be removed or replaced with an approved type. 3/10/2023
A17.1-1996 : Elevators 1.12 - Car enclosure 211.9 Tighten/repair car interior handrail. 10/30/2024
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 102.1 4x4 electrical box in machine room needs to have wiring inside box and cover installed. 10/30/2024