MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
No
|
No
|
The elevator control valve seeped an excessive amount of oil in testing, This control valve shall be repaired or replaced, was leaking back to tank. Closed the shutoff valve and elevator did not sink.
|
9/9/2024
|
|
A17.1-1996 : Elevators
|
1.15 - sign and operating device symbols
|
210.13
|
No
|
No
|
Car buttons & bezels illegible, fire service key switch is illegible
|
|
|
A17.1-1996 : Elevators
|
2.36 - Hydraulic Cylinders
|
302.3
|
No
|
No
|
Elevator failed 15 minute leak down test. Investigate loss of pressure and address. Oil was leaking back through control valve, needs repaired or replaced.
|
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
No
|
No
|
Provide written maintenance control program on site.
|
1/19/2023
|
|
A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
Yes
|
No
|
Unsealed
|
5/19/2022
|
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
No
|
No
|
OSV is not sealed. Perform test on or before next annual inspection.
|
1/19/2023
|