Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.15 - sign and operating device symbols 210.13 No No Car buttons & bezels illegible, fire service key switch is illegible
A17.1-1996 : Elevators 2.36 - Hydraulic Cylinders 302.3 No No Elevator failed 15 minute leak down test. Investigate loss of pressure and address. Oil was leaking back through control valve, needs repaired or replaced.
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No OSV is not sealed. Perform test on or before next annual inspection. 1/19/2023
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Provide written maintenance control program on site. 1/19/2023
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 No No The elevator control valve seeped an excessive amount of oil in testing, This control valve shall be repaired or replaced, was leaking back to tank. Closed the shutoff valve and elevator did not sink. 9/9/2024
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) Yes No Unsealed 5/19/2022