MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Excessive oil leakage in pit bucket. A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans, shall not exceed 5 gal before removal, shall be covered, and shall not be permitted to overflow. Note: Per the State of Missouri AHJ: "The use of oil recovery systems to return the hydraulic fluid back into the main reservoir by automatic means or by gravity feed prevents proper monitoring of the gland packing and seals", and "machine rooms cannot be used as containment areas.” Use of oil recovery systems may be considered for use as a temporary means of collecting excessive oil leakage until repairs to correct condition are made.
|
8/22/2023
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
5/19/2021
|
|
A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
101.3d
|
|
|
Machine room door shall be self-closing and self-locking . Sliding gate/door to be kept closed and locked.
|
2/23/2026
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1001.2(d)12
|
x
|
|
Rear doors shall open on Phase 2 fire service and normal operation via the the button on the COP.
|
2/14/2020
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1001.2(d)12
|
x
|
|
There shall be an audible and visual signal on fire service.
|
2/14/2020
|
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1001.2(b)(7)
|
|
|
Machine Room shall have proper Fire Extinguisher. Currently Carbon Dioxide type, shall be ABC type.
|
2/23/2026
|
|
A17.1-1996 : Elevators
|
2.4 - Machine space
|
100.5
|
|
|
Machine room lighting needs to be repaired, 1 or more bulbs not working and shall be guarded against breakage.
|
2/23/2026
|
|
A17.1-1996 : Elevators
|
2.4 - Machine space
|
100.5
|
|
|
Non-elevator related items shall not be stored in Machine Room. (welder and welding cart, welding screen, mobile cart, etc)
|
2/23/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
The front door re-opening device shall be operational.
|
5/19/2021
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)5
|
|
|
All freight doors are missing pull straps. Install pull straps on all freight doors.
|
8/22/2023
|