Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.3 - Operating control devices 1001.2(a)(3) The door open button on the COP shall be repaired or replaced. 8/10/2021
A17.1-1996 : Elevators 1.3 - Operating control devices 1001.2(a)(3) The door open button shall be operational. 6/8/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational with 24/7 support. 6/3/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 2/15/2025
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test 8/10/2021
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) x This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve. The valve shall be sealed and tagged after the category 5 test. 6/22/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide a code complaint MCP including onsite documents. 8/10/2021
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f x Phase 2 fire service still has to be tested. The door open button is not working. 6/22/2022
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f x Phase 2 fire service still has to be tested. The door open button is not working. 1/20/2023