A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Two-way communication means between the car and a location staffed by authorized personnel shall be provided.
|
3/2/2026
|
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspection)
|
Yes
|
No
|
This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve. The valve shall be sealed and tagged after the category 5 test.
|
6/22/2022
|
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
No
|
No
|
This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test
|
8/10/2021
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
The in car emergency telephone shall be operational with 24/7 support.
|
6/3/2020
|
|
A17.1-1996 : Elevators
|
1.3 - Operating control devices
|
1001.2(a)(3)
|
No
|
No
|
The door open button shall be operational.
|
6/8/2023
|
|
A17.1-1996 : Elevators
|
1.3 - Operating control devices
|
1001.2(a)(3)
|
No
|
No
|
The door open button on the COP shall be repaired or replaced.
|
8/10/2021
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
No
|
No
|
Provide a code complaint MCP including onsite documents.
|
8/10/2021
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1002.2f
|
Yes
|
No
|
Phase 2 fire service still has to be tested. The door open button is not working.
|
6/22/2022
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1002.2f
|
Yes
|
No
|
Phase 2 fire service still has to be tested. The door open button is not working.
|
1/20/2023
|
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
1002.2g (Standby Power Operation)
|
Yes
|
No
|
Emergency power tested and failed. When elevator switched from normal power to emergency power the overload switch in the machin room controller tripped. This did not allow elevator to frun on emergency power until switch was reset. Repair as needed.
|
|
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
211.2
|
Yes
|
No
|
Emergency power operation shall be tested.
|
3/2/2026
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator.
|
2/15/2025
|