Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 2/15/2025
A17.1-1996 : Elevators 1.17 - Standby power operation 1002.2g (Standby Power Operation) Yes No Emergency power tested and failed. When elevator switched from normal power to emergency power the overload switch in the machin room controller tripped. This did not allow elevator to frun on emergency power until switch was reset. Repair as needed.
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No The emergency/standby power shall be tested. 5/13/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational with 24/7 support. 6/3/2020
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) Yes No This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve. The valve shall be sealed and tagged after the category 5 test. 6/21/2022
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 6/8/2023
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Provide a code compliant MCP including onsite documents. 8/10/2021
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. 8/10/2021
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 No No A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. 6/8/2023