Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No 1.5 emergency light needs battery 6/19/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No 8.6.4.9 car top and inside of elevator need cleaned 4/1/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Note starter contacts need replaced for pump motor 4/1/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No 8.6.1.6.5 fire extinguisher hasn't been checked since 2016 4/1/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No needs current certificate posted in machine room 4/1/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No emergency light in elevator does not work 5/10/2021
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No machine room floor and under pump unit needs to be cleaned and all non essential items removed 4/1/2025
MO Minimum : Elevators (I) - Pits (I)1 No No drain in the pit drains out on a concrete area also any loss of oil from pit area 4/1/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency/auxiliary lighting shall work with power loss. Repeat violation from 2020. 6/10/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency/auxiliary lighting shall work with power loss. Repeat violation from 2020. 6/14/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No 0 Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly. (Provided by Elev Co.) 4/20/2023
MO Minimum : Elevators (I) - Pits (I)1 No No Clean Pit 4/20/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No Oil Collection bucket shall be in the elevator pit, not outside of pit 4/20/2023