Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No Repair machine room ventilation 8/14/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Repair phone in car 10/6/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency communications phone in car not working 3/10/2025
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Perform monthly fire service testing and document on log in machine room 3/13/2025
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No Provide existing battery backup lowering unit to work properly. 6/2/2025
A17.1-1996 : Elevators 1.17 - Standby power operation 1002.2g (Standby Power Operation) Yes No Failed Cat 1 standby power test. Re-inspection required
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No Overspeed valve is overdue for full load testing 3/13/2025
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b No No Repair machine room ventilation 3/13/2025
A17.1-1996 : Elevators 2.6 - Ventilation 1001.2(b)(6) No No Repair machine room ventilation 10/13/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State Elevator Certificate. 3/13/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state certificate in machine room 3/13/2025