Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide a code compliant MCP including onsite documents.
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 There is no MCP on-site.
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone is not working. The in car emergency telephone shall be operational.
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) x This elevator is equipped with an overspeed valve that was due for category 5 testing in 2022. No annual inspection was performed in 2022. The overspeed valve shall be tested with the rated load in 90 days.