Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Monthly firefighter service log shall be maintained on site 3/26/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Phase I the hat light is flashing indicating a fire in the machine room, it should be on a steady while on Phase I & II. Re-inspection required 2/13/2024
A17.1-1996 : Elevators 3.1 - Top-of-car stop switch 1001.2(c)(1) Replace car top stop switch. 11/3/2020
MO Minimum : Elevators (F) - Electrical Switches (F)1 x Stop switch handle on door controller is broken, needs to be replaced 11/9/2022