MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established. Repair/replace this phone for proper operation and passenger safety. Reinspection required.
|
10/17/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The elevator pit floor is covered in water due to the sump pump not working.The sump pump shall be repaired/replaced and the elevator pit shall be kept clean and dry.
|
10/3/2024
|
A17.1-2016 : Elevators
|
3.28 - Counterweight and counterweight buffer
|
8.11.2.1.3(m)
|
|
|
1) The roller-type guide shoes are showing some wear, the top right rear roller on guide shoe has a chunk out of it and needs replaced. Ref: 8.11.2.1.3(m)
|
11/30/2020
|
A17.1-1996 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
1001.2(e)(2)
|
x
|
|
1) Runby before counterweight strikes buffer is 4 inches. Minimum is 6 inches. Suspension ropes need to be shorten. Ref: 8.11.2.1.5(b)
|
1/28/2020
|
A17.1-1996 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
1001.2(e)(2)
|
x
|
|
1) Runby before counterweight strikes buffer is 4 inches. Minimum is 6 inches. Suspension ropes need to be shorten. Ref: 8.11.2.1.5(b)
|
11/26/2019
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1002.2f
|
x
|
x
|
2) Firefighters’ emergency operation did not meet applicable requirements when testing alternate landing signal. Seems to be a short in system. Ref: 8.11.2.2.6 Re-inspect in 15 days.
|
11/26/2019
|