Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established. Repair/replace this phone for proper operation and passenger safety. Reinspection required. 10/17/2023
MO Minimum : Elevators (I) - Pits (I)1 The elevator pit floor is covered in water due to the sump pump not working.The sump pump shall be repaired/replaced and the elevator pit shall be kept clean and dry. 10/3/2024
A17.1-1996 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 1001.2(e)(2) x 1) Runby before counterweight strikes buffer is 4 inches. Minimum is 6 inches. Suspension ropes need to be shorten. Ref: 8.11.2.1.5(b) 11/26/2019
A17.1-1996 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 1001.2(e)(2) x 1) Runby before counterweight strikes buffer is 4 inches. Minimum is 6 inches. Suspension ropes need to be shorten. Ref: 8.11.2.1.5(b) 1/28/2020
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f x x 2) Firefighters’ emergency operation did not meet applicable requirements when testing alternate landing signal. Seems to be a short in system. Ref: 8.11.2.2.6 Re-inspect in 15 days. 11/26/2019
A17.1-2016 : Elevators 3.28 - Counterweight and counterweight buffer 8.11.2.1.3(m) 1) The roller-type guide shoes are showing some wear, the top right rear roller on guide shoe has a chunk out of it and needs replaced. Ref: 8.11.2.1.3(m) 11/30/2020