Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures and monthly fire service testing records are missing. (This item is for notification purposes for future violation in 2022)
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required shall be provided in the machine room. 2023 documentation is blank, and no fire service logs are present.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Adjust up-thrust roller bearings for proper clearance to door hanger track.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Adjust up-thrust roller bearings for proper clearance to door hanger track. Note: On the fifth floor, the up-thrust is about to fall off.
A17.1-1996 : Elevators 1.7 - Car door or gate 204.4 x Car gate switch shall not register "closed" at greater than 2" open. 11/18/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display a current MO state operating certificate.
MO Minimum : Elevators (A) - Hoistways (A)16 Electrical box in hoistway between floors one and two is missing cover. Wiring is exposed.
MO Minimum : Elevators (A) - Hoistways (A)16 Electrical box in hoistway between floors one and two is missing cover. Wiring is exposed.
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 12/7/2023
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power annually.
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power annually. Note: Elevator failed to operate on emergency generator. 11/18/2024
conversion conversion n/a No current state certificate posted. 10/24/2017
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State certificate in machine room 3/18/2020
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Properly display current state operating certificate in the machine room.
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide a code compliant MCP including on-site documents.
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) x Standby power operation of the elevators shall be tested. 4/8/2021
A17.1-1996 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 107.1b x The counterweight runby is 0". The cables shall be shortened to provide code compliant counterweight runby. 12/14/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work with and without main power. 11/18/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work with and without main power. (2nd Notice) This violation must be corrected immediately.
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Two-way emergency communication shall be operational. 12/5/2022