A17.1-2016 : Elevators
|
2.13 - Governor, Overspeed Switch, and Seal
|
2.18.6
|
x
|
|
2.18.6.5 - Top of hoistway: Governor shall have an access door installed or remote set/reset governor installed, as to be able to test governor without being on cartop for safety setting.
|
4/17/2025
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Battery lowering shall work. Take corrective action and re-test.
|
4/17/2025
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.6(c) Stop Switch Inoperable in Fire Service (Re-Inspection)
|
x
|
|
In-car stop switch shall not be made ineffective during phase 1 recall.
|
4/17/2025
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
|
4/17/2025
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
4/17/2025
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire extinguisher is expired, have serviced or replaced
|
4/17/2025
|