MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Elevator currently not able to operate on emergency power. Water damage in the building damaged the transfer panel. Once fixed emergency power will need to be tested.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.2.7 x Need to test emergency power. 5/12/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) x Repair car door restrictor. 7/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting x Emergency lights are not working. 5/12/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 2.14.7.1.2 Minimum Illumination The lights in the car are not all working. There is some water damage. 5/31/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone is not working. 5/12/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Not able to finish inspection. Did not test the brakes, slide, crash the buffers/car & counterweights, safeties & governor, the door restrictor, 125% weight test. 5/12/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.17 - Drive machine brake 8.6.4.19.11 A17.1 2016 Ascending Overspeed Protection, Unintended Movement Devices, and Emg Brake x Perform unintended motion test. 8.6.4.19.11 (c) 4/20/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) 8.4.10 Emegency Operation and Signaling Devices x Earthquake protection is not working. 5/12/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Rooms and Machinery Spaces Machine room needs to be cleaned. 5/31/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.9 Cleaning of Car Tops Top of car needs to be cleaned. 5/31/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(g) Fire extinguisher needs to be serviced.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Clean debris from pit.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits The pit shall be kept clean and dry. Remove water from pit floor. 5/31/2023