Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not operating correctly. The ADA phone does not give a location and the operator is unable to confirm the location of the emergency. Check and repair the programming of this phone for proper operation and passenger safety. Reinspection required. 2/6/2024
MO Minimum : Elevators (H) - Machine Rooms (H)1 Machine room door shall be self closing self locking.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Repair inoperative emergency phone. 14day reinspection
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit Clean oil from elevator pit floor
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection x Elevator fail leak down test due to packing leakage. Replace packing to reduce leakage. Re-inspection required