Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The elevator ADA telephone inside the elevator is not operating correctly. The ADA phone does not give a location and the operator is unable to confirm the location of the emergency. Check and repair the programming of this phone for proper operation and passenger safety. Reinspection required. | 2/6/2024 |