Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting In car emergency light shall work.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x In car emergency bell shall work. 2/14/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Provide a current tested fire extinguisher in the elevator machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Replace the missing braille/tactile plates on the 2nd and 3rd floor.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Photo eye detectors on mechanical car door are not working and shall be repaired or replaced as needed. 2/14/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Provide a working door restrictor. 2/14/2024
MO Minimum : Elevators (H) - Machine Rooms (H)8 x Controller workspace is obstructed by door such that the controller door cannot be fully opened.
MO Minimum : Elevators (H) - Machine Rooms (H)2 The machine room door shall be self-closing and self-locking.
MO Minimum : Elevators (H) - Machine Rooms (H)8 x Location of 110v and mainline feeders shall be labeled in machine room (not sharpie).
MO Minimum : Elevators (S) - Fire Service (S)1 x Phase 2 halo ring is worn and unreadable, replace as needed. 2/14/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 3.26.10 x Battery lowering shall work and be tested.
A17.1-2016 : Elevators 1.2 - Stop Switches 2.26.2.5 x Stop switch shall work. It is water damaged.
A17.1-2016 : Elevators 1.4 - Sills and car floor 2.11.10.2 x Lobby lighting at first floor is less than 5fc.
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 2.14.7 x Car lighting - all lamps shall work. No 110v power connected.
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 2.14.7 x Lamps (overhead cab lighting) shall be guarded.
A17.1-2016 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work. There is no dial tone.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Hydraulic fluid contaminated with large quantity of water.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire alarm initiating devices (FAID) shall be connected and tested.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x Overspeed Valve test still needs to be conducted.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The required pressure/weight testing shall still be conducted.
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.3.4 x Machine room door shall be self-closing and self-locking. Lock shall not be defeated.
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.1.1 x Machine room door shall have proper fire rating and labeled as such.
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space x Machine room - remove combustible wood material from walls.
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 x Machine room - oil line shut off valve access obstructed by main line disconnect.
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 x Machine room disconnecting means shall be provided with a compliant mechanical auxiliary contact to disconnect the load from the auxiliary power supply.
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Hoistways shall be of solid construction. Repair multiple fire penetrations.
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Hoistways shall be of solid construction and fire rated. Remove wood materials from walls and setbacks.
A17.1-2016 : Elevators 3.2 - Car top light and outlet 2.14.7.1.4 x Cartop light does not work. No 110v.
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 x 2.2.5.1 - Pit lighting shall not be less than 10fc at the pit floor.
conversion conversion n/a Car emergency lighting does not work.
conversion conversion conversion - reinspect x Car door restrictor shall work. 5/22/2019