MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
x
|
|
Overspeed Valve test still needs to be conducted.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The required pressure/weight testing shall still be conducted.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
x
|
|
Controller workspace is obstructed by door such that the controller door cannot be fully opened.
|
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
x
|
|
Machine room door shall be self-closing and self-locking. Lock shall not be defeated.
|
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.1.1
|
x
|
|
Machine room door shall have proper fire rating and labeled as such.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Fire alarm initiating devices (FAID) shall be connected and tested.
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Two-way communication device shall work. There is no dial tone.
|
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7
|
x
|
|
Car lighting - all lamps shall work. No 110v power connected.
|
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7
|
x
|
|
Lamps (overhead cab lighting) shall be guarded.
|
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
x
|
|
Machine room disconnecting means shall be provided with a compliant mechanical auxiliary contact to disconnect the load from the auxiliary power supply.
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
3.26.10
|
x
|
|
Battery lowering shall work and be tested.
|
|
A17.1-2016 : Elevators
|
1.2 - Stop Switches
|
2.26.2.5
|
x
|
|
Stop switch shall work. It is water damaged.
|
|
A17.1-2016 : Elevators
|
3.2 - Car top light and outlet
|
2.14.7.1.4
|
x
|
|
Cartop light does not work. No 110v.
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Hoistways shall be of solid construction. Repair multiple fire penetrations.
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Hoistways shall be of solid construction and fire rated. Remove wood materials from walls and setbacks.
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5
|
x
|
|
2.2.5.1 - Pit lighting shall not be less than 10fc at the pit floor.
|
|
A17.1-2016 : Elevators
|
1.4 - Sills and car floor
|
2.11.10.2
|
x
|
|
Lobby lighting at first floor is less than 5fc.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Hydraulic fluid contaminated with large quantity of water.
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
8.6.4.8 Machine Room and Machinery Space
|
x
|
|
Machine room - remove combustible wood material from walls.
|
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
x
|
|
Machine room - oil line shut off valve access obstructed by main line disconnect.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
x
|
|
Location of 110v and mainline feeders shall be labeled in machine room (not sharpie).
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The machine room door shall be self-closing and self-locking.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Provide a current tested fire extinguisher in the elevator machine room.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Replace the missing braille/tactile plates on the 2nd and 3rd floor.
|
|
conversion
|
conversion
|
n/a
|
|
|
Car emergency lighting does not work.
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
In car emergency light shall work.
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Car door restrictor shall work.
|
5/22/2019
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
In car emergency bell shall work.
|
2/14/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Phase 2 halo ring is worn and unreadable, replace as needed.
|
2/14/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
Photo eye detectors on mechanical car door are not working and shall be repaired or replaced as needed.
|
2/14/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
Provide a working door restrictor.
|
2/14/2024
|