Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work. There is no dial tone. 2/6/2025
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 2.14.7 x Car lighting - all lamps shall work. No 110v power connected. 2/6/2025
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 2.14.7 x Lamps (overhead cab lighting) shall be guarded. 2/6/2025
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 x Machine room disconnecting means shall be provided with a compliant mechanical auxiliary contact to disconnect the load from the auxiliary power supply. 2/6/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 3.26.10 x Battery lowering shall work and be tested. 2/6/2025
A17.1-2016 : Elevators 1.2 - Stop Switches 2.26.2.5 x Stop switch shall work. It is water damaged. 2/6/2025
A17.1-2016 : Elevators 3.2 - Car top light and outlet 2.14.7.1.4 x Cartop light does not work. No 110v. 2/6/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Hoistways shall be of solid construction. Repair multiple fire penetrations. 2/6/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Hoistways shall be of solid construction and fire rated. Remove wood materials from walls and setbacks. 2/6/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 x 2.2.5.1 - Pit lighting shall not be less than 10fc at the pit floor. 2/6/2025
A17.1-2016 : Elevators 1.4 - Sills and car floor 2.11.10.2 x Lobby lighting at first floor is less than 5fc. 2/6/2025
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 2.14.7 x Lamps (overhead cab lighting) shall be guarded. 3/6/2025
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.3.4 x Machine room door shall be self-closing and self-locking. Lock shall not be defeated. 3/6/2025
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.1.1 x Machine room door shall have proper fire rating and labeled as such. 3/6/2025
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Machine room lighting shall be at least 19fc at base of controller. 3/6/2025
A17.1-2016 : Elevators 2.4 - Machine space 2.8.1 x In the machine room remove combustible wood material from walls of cover properly with fire rated approved materials. 3/6/2025
A17.1-2016 : Elevators 2.4 - Machine space 2.8.1 x Spray foam shall be removed or covered with proper fire preventative. 3/6/2025
A17.1-2016 : Elevators 2.6 - Ventilation 2.7.9.2 x Proper ventilation shall be provided, either natural or mechanical. 3/6/2025
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x A proper ABC rated fire extinguisher shall be provided, with current test tag. 3/6/2025
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.1 x NEC 409.110 - All industrial control panels, including disconnects within them, must be marked with their SCCR to indicate the maximum fault current they can safely withstand; this applies to any component within the panel that is part of the power circuit. 3/6/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Hoistway has spray foam throughout, spray foam shall be removed or covered with proper fire preventative. 3/6/2025
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.6 x Hoistway projections shall be covered, with covering at 75 degrees. 3/6/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 x Pit ladder is obstructed by conduit. Relocate conduit to acceptable location. 3/6/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 x Pit lighting shall be at least 10fc. 3/6/2025
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x Pit electrical piping, boxes, conduit, etc shall be of weather-resistant construction (wiring for pit light and light are not weather/water resistant). 3/6/2025
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x Pit service outlet is not GFCI. Replace with proper outlet in weather resistant box with cover. 3/6/2025
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.3.4 x Machine room door shall be self-closing and self-locking. Lock shall not be defeated. 2/6/2025
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.1.1 x Machine room door shall have proper fire rating and labeled as such. 2/6/2025
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space x Machine room - remove combustible wood material from walls. 2/6/2025
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 x Machine room - oil line shut off valve access obstructed by main line disconnect. 2/6/2025
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 2.14.7 x Lamps (overhead cab lighting) shall be guarded. 3/21/2025
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.1.1 x Machine room door shall have proper fire rating and labeled as such. 3/21/2025
A17.1-2016 : Elevators 2.6 - Ventilation 2.7.9.2 x Proper ventilation shall be provided, either natural or mechanical. Added 3/6/25 - In wall vent (added 2025) does not have fire damper/not fire resistant. Openings in machine rooms and space enclosures shall be protected with access doors having a fire protection rating conforming with the requirements of the building code. Wall vent shall be equipped with a spoke shutter in compliance with NFPA 72. 3/21/2025
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.1.1 x Machine room door shall have proper fire rating and labeled as such. 3/31/2025
A17.1-2016 : Elevators 2.6 - Ventilation 2.7.9.2 x Proper ventilation shall be provided, either natural or mechanical. Added 3/6/25 - In wall vent (added 2025) does not have fire damper/not fire resistant. Openings in machine rooms and space enclosures shall be protected with access doors having a fire protection rating conforming with the requirements of the building code. Wall vent shall be equipped with a smoke shutter in compliance with NFPA 72. 3/31/2025
conversion conversion n/a Car emergency lighting does not work.
conversion conversion conversion - reinspect x Car door restrictor shall work. 5/22/2019
MO Minimum : Elevators (H) - Machine Rooms (H)2 The machine room door shall be self-closing and self-locking.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Provide a current tested fire extinguisher in the elevator machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Replace the missing braille/tactile plates on the 2nd and 3rd floor.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Photo eye detectors on mechanical car door are not working and shall be repaired or replaced as needed. 2/14/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Provide a working door restrictor. 2/14/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting In car emergency light shall work.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x In car emergency bell shall work. 2/14/2024
MO Minimum : Elevators (S) - Fire Service (S)1 x Phase 2 halo ring is worn and unreadable, replace as needed. 2/14/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x Overspeed Valve test still needs to be conducted. 2/6/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The required pressure/weight testing shall still be conducted. 2/6/2025
MO Minimum : Elevators (H) - Machine Rooms (H)8 x Controller workspace is obstructed by door such that the controller door cannot be fully opened. 2/6/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Hydraulic fluid contaminated with large quantity of water. 2/6/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x All elevator FAID shall be tested. 3/6/2025
MO Minimum : Elevators (H) - Machine Rooms (H)8 x Location of 110v and mainline feeders shall be labeled in machine room (not sharpie). 2/6/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire alarm initiating devices (FAID) shall be connected and tested. 2/6/2025