MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
No non-elevator related equipment can be stored in elevator equipment room
|
11/11/2021
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car telephone shall be operational. The car currently is not equipped with a telephone line, so the phone and the phone monitor could not be tested.
|
5/22/2024
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
An ABC fire extinguisher with a current test tag shall be mounted convenient to the machine room door.
|
5/22/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
x
|
|
The data on the door operator tag shall be filled out.
|
5/22/2024
|
A17.1-2016 : Elevators
|
1.13 - Emergency exit
|
2.14.1.5
|
x
|
|
The car-top emergency exit shall be secured to prevent it from falling down the hoistway. If a chain is used, it shall be not more than 12" in length and have a factor of safety of not less than 5.
|
5/22/2024
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
2.1.6.1 - The overhead fasteners protruding through the ceiling of the overhead shall be cut off flush to prevent a hazardous situation.
|
5/22/2024
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.6(c) Stop Switch Inoperable in Fire Service (Re-Inspection)
|
x
|
|
The in car keyed stop switch shall not be made ineffective on phase one fire service.
|
5/22/2024
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
2.8.1
|
x
|
|
ASME Interpretation - Record Number 10-1496. The sump pump controls shall not be located in the elevator machine room. Customer may apply for a variance.
|
5/22/2024
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
2.8.1
|
x
|
|
The elevator machine and control equipment shall be located in a separate room or separated space designed as an elevator machine room or space and shall be accessible only to authorized personnel. The machine room is currently a shared space for electrical switch gear and shelving. Customer may apply for a variance.
|
5/22/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Non elevator related items in machine room
|
6/6/2024
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
2.8.1
|
x
|
|
ASME Interpretation - Record Number 10-1496. The sump pump controls shall not be located in the elevator machine room. Customer may apply for a variance.
|
6/12/2024
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
2.8.1
|
x
|
|
The elevator machine and control equipment shall be located in a separate room or separated space designed as an elevator machine room or space and shall be accessible only to authorized personnel. The machine room is currently a shared space for electrical switch gear and shelving. Customer may apply for a variance.
|