Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)4 No non-elevator related equipment can be stored in elevator equipment room 11/11/2021
MO Minimum : Elevators (H) - Machine Rooms (H)4 Non elevator related items in machine room 6/6/2024
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x 2.1.6.1 - The overhead fasteners protruding through the ceiling of the overhead shall be cut off flush to prevent a hazardous situation. 5/22/2024
A17.1-2016 : Elevators 1.13 - Emergency exit 2.14.1.5 x The car-top emergency exit shall be secured to prevent it from falling down the hoistway. If a chain is used, it shall be not more than 12" in length and have a factor of safety of not less than 5. 5/22/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.6(c) Stop Switch Inoperable in Fire Service (Re-Inspection) x The in car keyed stop switch shall not be made ineffective on phase one fire service. 5/22/2024
A17.1-2016 : Elevators 2.4 - Machine space 2.8.1 x ASME Interpretation - Record Number 10-1496. The sump pump controls shall not be located in the elevator machine room. Customer may apply for a variance. 5/22/2024
A17.1-2016 : Elevators 2.4 - Machine space 2.8.1 x The elevator machine and control equipment shall be located in a separate room or separated space designed as an elevator machine room or space and shall be accessible only to authorized personnel. The machine room is currently a shared space for electrical switch gear and shelving. Customer may apply for a variance. 5/22/2024
A17.1-2016 : Elevators 2.4 - Machine space 2.8.1 x ASME Interpretation - Record Number 10-1496. The sump pump controls shall not be located in the elevator machine room. Customer may apply for a variance. 6/12/2024
A17.1-2016 : Elevators 2.4 - Machine space 2.8.1 x The elevator machine and control equipment shall be located in a separate room or separated space designed as an elevator machine room or space and shall be accessible only to authorized personnel. The machine room is currently a shared space for electrical switch gear and shelving. Customer may apply for a variance. 6/12/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car telephone shall be operational. The car currently is not equipped with a telephone line, so the phone and the phone monitor could not be tested. 5/22/2024
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x An ABC fire extinguisher with a current test tag shall be mounted convenient to the machine room door. 5/22/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x The data on the door operator tag shall be filled out. 5/22/2024