A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
Light bulbs in cab need to be guarded to prevent injury to persons in event of breakage. Replace open type "egg crate" ceiling panels with solid panels or install plastic tubes.
|
12/29/2020
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display current state operating certificate in elevator machine room.
|
12/29/2020
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State certificate in machine room
|
12/6/2018
|
A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
x
|
|
OSV has no seal or tag. Customer was notified on last inspection, Re-inspection must be completed in 90 days
|
10/7/2022
|
A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
x
|
|
OVER SPEED VALVE HAS NO SEAL OR TAG / CUSTOMER NOTIFIED ON LAST INSPECTION. TEST MUST BE COMPLETED WITHIN 90 DAYS
|
7/13/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
x
|
|
OSV valve needs to be repaired or replaced. Re-inspection required
|
7/13/2023
|