Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current state operating certificate in elevator machine room. 12/29/2020
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 Light bulbs in cab need to be guarded to prevent injury to persons in event of breakage. Replace open type "egg crate" ceiling panels with solid panels or install plastic tubes. 12/29/2020
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV has no seal or tag. Customer was notified on last inspection, Re-inspection must be completed in 90 days 10/7/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x OSV valve needs to be repaired or replaced. Re-inspection required 7/13/2023
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OVER SPEED VALVE HAS NO SEAL OR TAG / CUSTOMER NOTIFIED ON LAST INSPECTION. TEST MUST BE COMPLETED WITHIN 90 DAYS 7/13/2023
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State certificate in machine room 12/6/2018