MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of current state operating certificate shall be properly displayed in machine room
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
1/9/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone in car does not work, appears to be an issue with the line. Re-inspection required
|
1/9/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire extinguisher in machine room is expired. Replace or have serviced
|
1/9/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
x
|
|
OSV is overdue for testing as noted in last inspection. Perform required testing, seal & tag within 90 days. Re-inspection required
|
1/9/2023
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
Perform OSV test. Tag and seal upon completion.
|
1/5/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone failed to operate
|
1/9/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces
|
|
|
Remove all non elevator related wiring from machine room, including coaxial cable & power for tv in adjacent room
|
1/9/2023
|
A17.1-1996 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
102.1
|
|
|
Remove unused wiring connected to exhaust fan switch in machine room or use power fan in accordance with NFPA 70
|
1/9/2023
|
A17.1-1996 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
102.1
|
|
|
Wiring for exhaust fan in machine room shall be made permanent, be grounded & be properly enclosed in conduit per NFPA 70
|
1/9/2023
|