Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection) x Repair the fire service and test all smoke and heat initiating devices. The Flashing hat was not working. 9/29/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency phone is not working. 9/29/2022
A17.1-2016 : Elevators 4.5 - Access to Hoistway 2.12.7 x The hoistway access, on the top level, is out of the lowering range. 9/29/2022
A17.1-2016 : Elevators 2.14 - Code data plate 8.9 x Provide a code data plate that reflects the new inspection code. 9/29/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates does not have a crosshead data tag, provide crosshead data tag
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x the emergency lights go out as soon as the alarm button is pressed and do not come back on, repair emergency light system 6/5/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x the alarm bell did not work on battery power 7/12/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x the emergency phone did not work, no dial tone 7/12/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting open egg crate ceiling panels, light tubes shall be guarded
MO Minimum : Elevators (H) - Machine Rooms (H)4 do not store non-elevator related material in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods the top direction limit was not activated during the stop ring test,
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements car top work light bulb was missing
MO Minimum : Elevators (K) - Car Platforms and Car Slings (K)4 does not have a crosshead data tag
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting elevator has an open egg crate drop ceiling, the light tube shall be guarded against breakage