Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (K) - Car Platforms and Car Slings (K)4 does not have a crosshead data tag
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting elevator has an open egg crate drop ceiling, the light tubes shall be guarded against breakage
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting open egg crate ceiling panels, the light tubes shall be guarded
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x adjust the door restrictor, it did not work, the hook did not catch 6/5/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone not operational ( no power to controller) 6/5/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x the alarm bell did not work on battery power 7/12/2021