Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Supply required monthly FFS test log 7/30/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No emg phone not working 5/20/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency alarm not working on battery power, emergency phone ok. 5/7/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Tile at main floor landing level presents a trip hazard, repair tile flush with elevator landing sill. 4/16/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No machine this is room door not self closing or self locking. This is a repeat violation reinsp. required 4/16/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Mach.room door needs to be self closing an self locking 4/16/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No mach room door not self closing or self locking 4/16/2025
MO Minimum : Elevators (I) - Pits (I)1 No No pit has standing water an oil in it 4/16/2025
MO Minimum : Elevators (I) - Pits (I)1 No No water an oil in pit needs to be cleaned up 4/16/2025
MO Minimum : Elevators (I) - Pits (I)1 No No Oil in pit. 4/16/2025
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Pit light not working. 4/16/2025
MO Minimum : Elevators (I) - Pits (I)1 No No pit floor covered in oil debris in pit reinsp required 4/16/2025
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No pit lt not working reinsp required 4/16/2025
MO Minimum : Elevators (K) - Car Platforms and Car Slings (K)6 No No lower guide shoes missing inserts causing excessive movement of car reinsp required 4/16/2025
MO Minimum : Elevators (K) - Car Platforms and Car Slings (K)6 No No Rail guide shoes worn, causing car movement. 4/16/2025
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No Fire int. device not working top floor that was added 5/24/2019
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.13.1(l)(Door Restrictor) Yes No door restrictor on front door has been removed replace or repair 10/1/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No emg phone not working no line voltage 14 days to fix or repair 10/1/2024
A17.1-2016 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 No No leak dn test was 3/4 inch. in 15 mins gate valve closed an no noticeable difference in oil tank futher testing needed reinsp required 8.6.5.14.2(b) 4/16/2025
A17.1-2016 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 No No replace packing on cyl head an provide 5 gal oil collection can reinsp required 4/16/2025
conversion conversion n/a No No Pit was wet and filthy [2yr notice] 7/30/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No no current cirt of operation displayed 4/16/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No CURRENT CIRT NOT DISPLAYED 4/16/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No no current insp cirt posted 4/16/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current operating certificate in machine room when received. 4/16/2025