Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)1 pit has standing water an oil in it
MO Minimum : Elevators (H) - Machine Rooms (H)2 Mach.room door needs to be self closing an self locking
MO Minimum : Elevators (H) - Machine Rooms (H)2 mach room door not self closing or self locking
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate CURRENT CIRT NOT DISPLAYED
MO Minimum : Elevators (I) - Pits (I)1 water an oil in pit needs to be cleaned up
MO Minimum : Elevators (I) - Pits (I)1 Oil in pit.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light not working.
MO Minimum : Elevators (K) - Car Platforms and Car Slings (K)6 Rail guide shoes worn, causing car movement.
conversion conversion n/a Pit was wet and filthy [2yr notice] 7/30/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Supply required monthly FFS test log 7/30/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate no current cirt of operation displayed
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Tile at main floor landing level presents a trip hazard, repair tile flush with elevator landing sill.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate in machine room when received.
MO Minimum : Elevators (H) - Machine Rooms (H)2 machine this is room door not self closing or self locking. This is a repeat violation reinsp. required
MO Minimum : Elevators (I) - Pits (I)1 pit floor covered in oil debris in pit reinsp required
MO Minimum : Elevators (K) - Car Platforms and Car Slings (K)6 lower guide shoes missing inserts causing excessive movement of car reinsp required
A17.1-2016 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 leak dn test was 3/4 inch. in 15 mins gate valve closed an no noticeable difference in oil tank futher testing needed reinsp required 8.6.5.14.2(b)
A17.1-2016 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 replace packing on cyl head an provide 5 gal oil collection can reinsp required
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) pit lt not working reinsp required
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate no current insp cirt posted
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.13.1(l)(Door Restrictor) x door restrictor on front door has been removed replace or repair 10/1/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x emg phone not working no line voltage 14 days to fix or repair 10/1/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x emg phone not working 5/20/2022
MO Minimum : Elevators (S) - Fire Service (S)1 x Fire int. device not working top floor that was added 5/24/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency alarm not working on battery power, emergency phone ok. 5/7/2024