MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
emg phone not working
|
5/20/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency alarm not working on battery power, emergency phone ok.
|
5/7/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
machine this is room door not self closing or self locking. This is a repeat violation reinsp. required
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Mach.room door needs to be self closing an self locking
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
mach room door not self closing or self locking
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
pit has standing water an oil in it
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
water an oil in pit needs to be cleaned up
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Oil in pit.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
pit floor covered in oil debris in pit reinsp required
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
pit lt not working reinsp required
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit light not working.
|
|
MO Minimum : Elevators
|
(K) - Car Platforms and Car Slings
|
(K)6
|
|
|
Rail guide shoes worn, causing car movement.
|
|
MO Minimum : Elevators
|
(K) - Car Platforms and Car Slings
|
(K)6
|
|
|
lower guide shoes missing inserts causing excessive movement of car reinsp required
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Fire int. device not working top floor that was added
|
5/24/2019
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
no current cirt of operation displayed
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
CURRENT CIRT NOT DISPLAYED
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certificate in machine room when received.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
no current insp cirt posted
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Supply required monthly FFS test log
|
7/30/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Tile at main floor landing level presents a trip hazard, repair tile flush with elevator landing sill.
|
|
A17.1-2016 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
8.6.4.13.1(l)(Door Restrictor)
|
x
|
|
door restrictor on front door has been removed replace or repair
|
10/1/2024
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
emg phone not working no line voltage 14 days to fix or repair
|
10/1/2024
|
A17.1-2016 : Elevators
|
5.11 - Plunger and Cylinder
|
8.6.5.5
|
|
|
leak dn test was 3/4 inch. in 15 mins gate valve closed an no noticeable difference in oil tank futher testing needed reinsp required 8.6.5.14.2(b)
|
|
A17.1-2016 : Elevators
|
5.11 - Plunger and Cylinder
|
8.6.5.5
|
|
|
replace packing on cyl head an provide 5 gal oil collection can reinsp required
|
|
conversion
|
conversion
|
n/a
|
|
|
Pit was wet and filthy [2yr notice]
|
7/30/2020
|