Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates There is not “In Case of Fire” signage at each landing as required by the building code. 3/4/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods x The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed. 6/9/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 2.14.7.1.3 Provide Auxiliary Lighting x The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. Need to repair to operate. Re-inspection required 3/24/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency communication is inoperable. Re-inspection required 3/24/2026