MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
pit has oil on floor an other debris oil sorb ect.
|
12/3/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
no current cirt displayed
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
phone had busy signal when tested
|
10/24/2024
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
phone not working
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Wiring in hoistway not enclosed
|
9/5/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Fire serv. signage in car not correct
|
9/5/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
None elev. related wiring in hoistway
|
9/5/2018
|
A17.1-2016 : Elevators
|
2.36 - Hydraulic Cylinders
|
8.6.5.5.2 Collection of Oil Leakage
|
x
|
|
oil pumpback unit in pit needs to be removed
|
12/3/2021
|