MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone not working
|
5/24/2022
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone not working
|
1/5/2022
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
|
|
lot of debris in pit 106.2a
|
1/1/2023
|
A17.1-1996 : Elevators
|
4.4 - Hoistway door locking devices
|
111
|
x
|
x
|
Freight Bi-Parting Landing Door Mechanical lock broken doors could be opened by separating with car away from landing.
|
10/17/2018
|
A17.1-1996 : Elevators
|
4.1 - Car platform guard
|
203.9
|
|
|
needs new platform guard installed
|
1/1/2023
|
A17.1-1996 : Elevators
|
4.1 - Car platform guard
|
203.9
|
|
|
toe guard needs to be replaced only covers less than half of opening
|
1/1/2023
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
phone not working
|
10/18/2020
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency Telephone Incoming Line is bad must replace or repair & retest.
|
1/6/2023
|
A17.1-2016 : Elevators
|
1.2 - Stop Switches
|
8.11.2.1.1(b)
|
|
|
In car stop switch works in up direction but not down. May tie in to phase 2 key switch problem. Used as no rider so left running
|
1/23/2023
|
A17.1-2016 : Elevators
|
1.15 - sign and operating device symbols
|
8.6.1.6.7
|
|
|
In case of fire don't use elevator signage needed
|
1/1/2023
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone not working
|
11/16/2022
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
x
|
|
Phase 2 key switch not working
|
11/16/2022
|
A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
8.6.5.16.5
|
|
|
Overspeed valve tripping above 140% of down speed. Rusted up so can't adjust
|
1/1/2023
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
FS No Audible or Visual Signals on Phase I recall.
|
10/12/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Phase II operation not working.
|
10/12/2018
|