Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone is not working. Re-inspection required 1/10/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting The elevator has an egg crate type of ceiling, the fluorescent bulbs need to have a plastic guard around them in case of shattering and broken glass won't fall on anyone
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Repair or replace broken light on cartop
MO Minimum : Elevators (H) - Machine Rooms (H)2 The fence around the pumping unit shall be repaired and anchored more securely. The machine room gate shall be self closing & locking.
MO Minimum : Elevators (I) - Pits (I)1 Pit needs to be clean & dry
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing Is was noted on last inspection that OSV test was to be performed on next annual inspection. OSV is not sealed.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written maintenance control program shall be kept on site for each elevator.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written maintenance control program shall be kept on site for each elevator.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.2 - Car top light and outlet 8.11.2.1.3(b) Car top light is not working. Repair broken light.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Elevator pit is covered in hydraulic fluid. Clean elevator pit.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be on display in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current operating certificate shall be displayed in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room