Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone is not working. Re-inspection required 1/10/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting The elevator has an egg crate type of ceiling, the fluorescent bulbs need to have a plastic guard around them in case of shattering and broken glass won't fall on anyone
MO Minimum : Elevators (H) - Machine Rooms (H)2 The fence around the pumping unit shall be repaired and anchored more securely. The machine room gate shall be self closing & locking.
MO Minimum : Elevators (I) - Pits (I)1 Pit needs to be clean & dry
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current operating certificate shall be displayed in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be on display in the machine room
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.2 - Car top light and outlet 8.11.2.1.3(b) Car top light is not working. Repair broken light.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written maintenance control program shall be kept on site for each elevator.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written maintenance control program shall be kept on site for each elevator.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Repair or replace broken light on cartop
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Elevator pit is covered in hydraulic fluid. Clean elevator pit.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing Is was noted on last inspection that OSV test was to be performed on next annual inspection. OSV is not sealed.