MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Make emergency bell operational when 110V source is removed.
|
6/18/2019
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
In car emergency bell shall be operational when 110v source is removed.
|
5/26/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Confirm the hydraulic jack in code compliant and not a single bottom type, or apply for a variance exception. Provide on-site documentation of jack type.
|
5/26/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO state operating certificate shall be posted in the elevator machine room.
|
6/1/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
8.6.5.8 - Confirm the hydraulic jack is code compliant and not a single bottom type or apply for a variance extension.
|
6/1/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
The in car emergency light shall be operational.
|
6/1/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Make emergency light operational.
|
6/1/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.11 - Plunger and Cylinder
|
8.6.5.8 Safety Bulkhead
|
x
|
|
Need to determine if this unit is a single bottom jack. If it is determined to be a single bottom jack, corrective measures shall be taken. It unit is double bottom type, verification documentation shall be kept in the machine room.
|
8/17/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)5
|
|
|
Pit ladder shall extend no less than 30" above pit access door sill.
|
9/13/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit light switch shall be accessible from pit access door.
|
9/13/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.36 - Hydraulic Cylinders
|
8.6.5.5.2 Collection of Oil Leakage
|
|
|
The hydraulic tank drip pan has an excessive amount of oil, it shall be cleaned.
|
9/14/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
9/14/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site.
|
9/14/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site.
|
9/14/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
9/14/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device.
|
9/14/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean the pit of dirt, debris, and oil.
|
9/14/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)5
|
|
|
A pit ladder shall be provided.
|
9/14/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
The means to restrict opening of the car door shall be operational.
|
10/9/2024
|